Summary
Successful exploitation of these vulnerabilities could allow an attacker with access to the IT network to manipulate industrial control devices without requiring physical access, specialized insider knowledge, or advanced tooling.
The following versions of Panduit IntraVUE are affected:
- IntraVUE <=3.2.1a14
| CVSS | Vendor | Equipment | Vulnerabilities |
|---|---|---|---|
| v3 10 | Pronetiqs | Panduit IntraVUE | Plaintext Storage of a Password, Unintended Proxy or Intermediary (‘Confused Deputy’), Exposure of Sensitive System Information to an Unauthorized Control Sphere, Inadequate Encryption Strength |
Background
- Critical Infrastructure Sectors: Critical Manufacturing, Energy, Information Technology, Water and Wastewater
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: Netherlands
Vulnerabilities
CVE-2026-40430
Pronetiqs IntraVUE Versions 3.2.1a14 and prior have a plaintext storage of a password vulnerability that could expose cleartext credentials through the API.
Affected Products
Panduit IntraVUE
Pronetiqs
Pronetiqs IntraVUE: <=3.2.1a14
known_affected
Remediations
Vendor fix
Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.
Mitigation
For further questions, please contact Pronetiqs at info@pronetiqs.com.
mailto:info@pronetiqs.com
Relevant CWE: CWE-256 Plaintext Storage of a Password
Metrics
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 7.5 | HIGH | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N |
| 4.0 | 8.7 | HIGH | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N |
CVE-2026-42933
Pronetiqs IntraVUE versions 3.2.1a14 and prior have an unintended proxy or intermediary vulnerability which could allow an attacker to use an active proxy, which would bypass OT segmentation.
Affected Products
Panduit IntraVUE
Pronetiqs
Pronetiqs IntraVUE: <=3.2.1a14
known_affected
Remediations
Vendor fix
Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.
Mitigation
For further questions, please contact Pronetiqs at info@pronetiqs.com.
mailto:info@pronetiqs.com
Relevant CWE: CWE-441 Unintended Proxy or Intermediary (‘Confused Deputy’)
Metrics
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 10 | CRITICAL | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H |
| 4.0 | 10 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H |
CVE-2026-44955
Pronetiqs IntraVUE versions 3.2.1a14 and prior have an exposure of sensitive system information to an unauthorized control sphere vulnerability which could allow for asset discovery by unauthenticated users.
Affected Products
Panduit IntraVUE
Pronetiqs
Pronetiqs IntraVUE: <=3.2.1a14
known_affected
Remediations
Vendor fix
Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.
Mitigation
For further questions, please contact Pronetiqs at info@pronetiqs.com.
mailto:info@pronetiqs.com
Relevant CWE: CWE-497 Exposure of Sensitive System Information to an Unauthorized Control Sphere
Metrics
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 5.3 | MEDIUM | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N |
| 4.0 | 6.9 | MEDIUM | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N |
CVE-2026-50044
Pronetiqs IntraVUE versions 3.2.1a14 and prior have an inadequate encryption strength vulnerability which could allow an attacker to steal admin credentials via weak hash or a pass-the-hash attack.
Affected Products
Panduit IntraVUE
Pronetiqs
Pronetiqs IntraVUE: <=3.2.1a14
known_affected
Remediations
Vendor fix
Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.
Mitigation
For further questions, please contact Pronetiqs at info@pronetiqs.com.
mailto:info@pronetiqs.com
Relevant CWE: CWE-326 Inadequate Encryption Strength
Metrics
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 6.8 | MEDIUM | CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:N |
| 4.0 | 7.6 | HIGH | CVSS:4.0/AV:N/AC:H/AT:P/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N |
CVE-2026-28698
Pronetiqs IntraVUE versions 3.2.1a14 and prior have an exposure of sensitive system information to an unauthorized control sphere vulnerability which could expose the underlying host/share filesystem.
Affected Products
Panduit IntraVUE
Pronetiqs
Pronetiqs IntraVUE: <=3.2.1a14
known_affected
Remediations
Vendor fix
Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.
Mitigation
For further questions, please contact Pronetiqs at info@pronetiqs.com.
mailto:info@pronetiqs.com
Relevant CWE: CWE-497 Exposure of Sensitive System Information to an Unauthorized Control Sphere
Metrics
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 8.6 | HIGH | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N |
| 4.0 | 9.2 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:H/SI:N/SA:N |
Acknowledgments
- Phlebas of Lumintel reported these vulnerabilities to CISA
Legal Notice and Terms of Use
This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.
Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
Revision History
- Initial Release Date: 2026-07-23
| Date | Revision | Summary |
|---|---|---|
| 2026-07-23 | 1 | Initial Publication |